Software Manual 118
Services Tab
• Once the desired information has been selected, click on the NEXT button and the next dialog window will appear:
Event Type: An event is TRUE when:
Data Match: The value of the register is equal to the alarm value.
Data Mismatch: The value of the register is not equal to the alarm value.
Absolute High: The value of the register exceeds the alarm's value.
Absolute Low: The value of the register falls below the alarm's value.
Deviation High: The value of the register exceeds the setpoint by an amount equal to or greater than the alarm's value.
Deviation Low: The value of the register falls below the setpoint by an amount equal to or greater than the alarm's value.
Out of Band: The value of the register moves outside a band, equal in width to twice the alarm's value and centered on the
setpoint.
In Band: The value of the register moves inside a band, equal in width to twice the alarm's value and centered on the set-
point.
Alarm Value (Required): An event is TRUE when:
Data Match: The value of the register is equal to the alarm value.
Data Mismatch: The value of the register is not equal to the alarm value.
Absolute High: The value of the register exceeds the alarm's value.
Absolute Low: The value of the register falls below the alarm's value.
Deviation High: The value of the register exceeds the setpoint by an amount equal to or greater than the alarm's value.
Deviation Low: The value of the register falls below the setpoint by an amount equal to or greater than the alarm's value.
Out of Band: The value of the register moves outside a band, equal in width to twice the alarm's value and centered on the
setpoint.
In Band: The value of the register moves inside a band, equal in width to twice the alarm's value and centered on the set-
point.
Activation Delay (in sec) (Required): Enter the value for the Activation Delay. This is used to indicate how long the
alarm condition must exist (in seconds) before the alarm will become active.
Clear Event/Alarm Condition: Select the desired option to clear an event condition.
Automatic: Allows an event condition to clear to an inactive state when the input meets configured conditions.